1)the maximum phase current of a side is less than 20% of the rated current, it is not sentenced to the side;
2)2) the maximum value of the phase current is greater than 120% of the rated current of the side;
3)3) served as the start of one side of the current than before the start of the increase.In the case of the above three conditions are not satisfied, such as one side at the same time meet the following conditions, then sentenced to CT break:
1)only one phase current is zero;
2) the remaining two phase currents are equal before starting the current.
3.3.2 differential current limit alarmIf the difference is greater than 15% of the rated current, after more than 10s discriminant, issued a warning **. Differential current limit, but not locked differential protection. The function and the monitoring function of the AC sampling circuit of the protection device
3.4 loss of magnetic protection
Generator loss of excitation protection for generator excitation current abnormal decrease or disappear completely lost magnetic fault protection, by the generator stator impedance as the main criterion, combined with low voltage and generator excitation system low voltage as auxiliary criterion, and have TV disconnection locking function, TV break send alarm **.
Its action logic is as follows:
![专业制造发电机保护测控装置定做](//l.b2b168.com/2019/01/26/09/201901260917544288964.jpg)
2.2 Main technical performance
Precise working range of 2.2.1 sampling circuit (10% error)
Voltage: 0.4 V ~ 120V
Current: 0.08In20In
2.2.2 contact capacity
Signal circuit contact current carrying capacity 400VA
Signal circuit contact fault arc capacity 60VA
2.2.3 tripping current
Breaker trip current 0.5A~4A (order indication)
The circuit breaker closing current 0.5A~4A (the order stated)
2.2.4 precision of various components
Current component: <5%
Voltage components: <5%
Time element: 0s-1s, the error is not more than 40ms;
1s above, the error is not more than < + 2.5%;
Frequency deviation: <0.02Hz
![专业制造发电机保护测控装置定做](//l.b2b168.com/2019/01/26/09/201901260917579263844.jpg)
Three、Software function deion
3.1. differential quick break protection
When any phase difference current is greater than the value of the differential speed, the protection action is stopped. Fast removal of generators in the case of a serious fault in the area of the generator. Differential speed determine the value should be able to avoid the external fault of the maximum unbalanced current, and taking into account the current transformer saturation factor, generally take 3 to 8 times the rated current
3.2.Ratio differential protection
Using the conventional ratio differential principle, the equations of motion are as follows:
Id > Icd (Ir Ir0)
Id - Icd > Kcd ·(Ir- Ir0) (Ir ≥ Ir0)
At the same time to meet the above two equations, the ratio of the differential element action. Among them, Id for the differential current, Ir for the braking current, Kcd for
Ratio braking coefficient, Icd is the threshold value of the differential current, and Ir0 is the turning point of the current value.
![专业制造发电机保护测控装置定做](//l.b2b168.com/2019/01/26/09/201901260917566578534.jpg)
1.3 function configurationFunction configuration of SAI3880D digital generator differential protection deviceDifferential quick break, ratio brake differential, CT disconnection locking differential, CT disconnection alarm, stator overvoltage protection, stator ground fault protection, overload alarm, anti time overcurrent protectionFunction configuration of backup protection device for SAI3881D digital generatorTransverse differential protection, loss of excitation protection, rotor one point grounding protection, rotor two points grounding protection composite voltage over current protection, inverse time negative sequence overcurrent protection, Pt disconnection alarm, non electricity protection (generator water shutoff, and the generator thermal, generator excitation accident, main steam valve closed),