EPS消防应急电源该如何选择?选型原则是什么?
EPS消防应急电源该如何选择?选型原则是什么?
EPS emergency power supply, how to choose? Selection What are the principles?
一、负载容量选型原则:
因电动机的启动冲击,与其配用的集中应急电源容量按以下容量选配。
1、电动机变频启动时,应急电源容量可按电动机容量1.2倍选项配。
2、电动机软启动时,应急电源容量应不小于电动机容量的2.5倍。
3、电动机Y-△启动时,应急电源应不小于电动机容量的3倍。
4、电动机直接启动时,应急电源容量应不小于电动机容量的5倍。
5、混合负载中,大电机的容量若小于总负载容量的1/7.
A load capacity of the principle of selection:
Due to the impact of motor starting, its equipped with a centralized emergency power capacity in the following capacity matching.
1, the motor frequency starts, emergency power supply capacity can be 1.2 times the option with the motor capacity.
2, motor soft start, the emergency power supply capacity should be not less than 2.5 times the motor capacity.
3, the motor Y-△ start, the emergency power supply should not be less than three times the motor capacity.
4, motor direct start-up, emergency power supply capacity should be not less than five times the capacity of the motor.
5, the mixed load, the maximum capacity of the motor is smaller than if the total load capacity of 1/7.
二、选型容量计算方法:
1、柏克YJ系列或YJS系列用于带应急灯具负载时:
(1)当负载为电子镇流器日光灯,EPS容量计算方法:EPS容量=电子镇流器日光灯功率和×1.1倍。
(2)当负载为电感镇流器日光灯,EPS容量计算方法:EPS容量=电感镇流器日光灯功率和×1.5倍。
(3)当负载为金属卤化物灯或金属钠灯,EPS容量计算方法:EPS容量=金属卤化物灯或金属钠灯功率和×1.6倍。
Second, the selection of capacity calculation method:
1, Burke YJ series or YJS series used with emergency lighting load:
(1) When the load is electronic ballast fluorescent, EPS capacity calculation method: EPS capacity = electronic ballast fluorescent lamp power and × 1.1-fold.
(2) When the load is inductive ballast fluorescent, EPS capacity calculation method: EPS capacity = inductive ballast fluorescent lamp power and × 1.5-fold.
(3) When the load is a metal halide lamp or a metal sodium, EPS capacity calculation method: EPS capacity = sodium metal or a metal halide lamp power and × 1.6 times.
2、当YJS系列用于带混合负载时,EPS容量的计算方法:
(1)当EPS带多台电动机且都同时启动时,则EPS的容量应遵循如下原则:
EPS容量=变频启动电动机功率之和+软启动电动机功率之和×2.5+星三角启动机功率之和×3+直接启动电动机之和×5倍
2, when the YJS series is used with mixed loads, EPS capacity calculation method:
(1) When the EPS with multiple motors and are simultaneously activated, then the capacity of the EPS should follow the following principles:
EPS capacity = frequency start the motor power and + soft start motor power of × 2.5 + star delta starter motor and the power of the motor is started directly × 3 + and × 5 times the
(2)当EPS带多台电动机且都分别单台启动时(不是同时启动),则EPS的容量应遵循如下原则:
EPS容量=各个电动机功率之和,但必须满足以下条件:
※ 上述电动机中直接启动的大的单台电动机功率是EPS容量的1/7.
※ 星三角启动的大的单台电动机功率是EPS容量的1/4.
※ 软启动的大的单台电动机功率是EPS容量的1/3.
※ 变频启动的大的单台电动功率不大于EPS的容量.
※ 如果不满足上述条件,则应按上述条件中的大数调整EPS的容量,电动机启动时的顺序为直接启动在先,其次是星三角的启动,有软启动的再启动,后是变频启动的再启动.
(2) When more than one motor and belt EPS were all single boot (not simultaneously start), then the capacity of the EPS should follow the following principles:
EPS capacity = sum of all motor power, but must meet the following conditions:
※ The motor started directly largest single motor power is the EPS capacity of 1/7.
※ star delta starter largest single motor power is the EPS capacity of 1/4.
Soft start ※ largest single motor power is the EPS capacity of 1/3.
※ inverter startup largest single electric power less than EPS capacity.
※ If not the above conditions shall be the maximum number of the above conditions the capacity to adjust the EPS, the motor startup sequence is started directly first, followed by the star-delta start-up, a soft start re-start, and finally the frequency conversion re-start.
(3)当YJS系列EPS带混合负载时EPS应遵循如下原则:
EPS容量=所有负载总功率之和,但必须中以下六条件,若不满足,再按照其*的容量确定EPS容量.
※ 负载中直接同时启动的电动机功率之和是EPS容量的1/7
※ 负载中星三角同时启动电动机功率之和是EPS容量的1/4
※ 负载中软启动同时启动的电动机功率之和是EPS容量的1/3
※ 负载中变频启动同时启动电动机功率之和不大于EPS的容量.
※ 同时启动的电动机当量功率之和不大于EPS的容量.
电动机功率容量=直接启动的电动机总功率x5+星三角同时启动的电动机总功率x3+软启动同时启动的电动机总功率x2.5+变频启动且同时启动的电动机总功率
若电动机前后启动时间相差大于1分钟均不视为同时启动。
※ 同时启动的所有负载(含非电动机负载)的当量功率之和不大于EPS的容量。
同时启动的所有负载的功率之和=同时启动的非电动机总功率×功率因数+电动机当量总功率。
(3) When the YJS series EPS EPS with mixed loads should follow the following principles:
EPS capacity = total power of all loads, but it must in the following six conditions, if not met, then the capacity determined in accordance with one of the largest EPS capacity.
※ load directly activated simultaneously and that the EPS motor power capacity of 1/7
※ star delta load and start the motor power and is EPS capacity of 1/4
※ load soft start motor power of simultaneously started and is EPS capacity of 1/3
※ load and start motor power inverter startup and not greater than the capacity of the EPS.
※ started simultaneously equivalent power of the motor is not greater than the capacity of EPS.
Motor power capacity = direct start of motor power x5 + star delta start simultaneously x3 + motor power soft-start and start the motor power x2.5 + inverter motor starts and the total power simultaneously started
If the motor before start time difference than 1 minute are not regarded as the same time.
※ started simultaneously all loads (including non-motor loads) of equivalent power is not greater than the capacity of EPS.
Started simultaneously in all the power load and simultaneously start = total power × non-motor motor power factor + Equivalent total power.
EPS电源又称EPS、消防应急电源,全称Emergency Power Supply(紧急电力供给),国家新标准为GB17945-2010《消防应急照明与疏散指示系统》。
是当今重要建筑物中为了电力**和消防安全而采用的一种应急电源。它主要由输入输出单元、充电模块、电池组、逆变器、监控器、输出切换装置等部分组成。广泛应用于节能供电、大楼照明、道路交通照明、隧道照明、电力、工矿企业、消防电梯等。
其原理为:在市电正常时,由市电经过输出切换装置给重要负荷供电,同时充电器为蓄电池进行充电或浮充;当市电断电后或电压**出供电范围,控制器启动逆变器,同时输出切换装置将市电供电状态立即切换到逆变器供电,为负荷设备提供应急供电;当市电恢复时,应急电源将恢复为市电供电。
EPS是以解决应急照明、事故照明、消防设施等一级负荷供电设备为主要目标,提供一种符合消防规范的具有独立回路的应急供电系统,该系统能够在应急状态下提供紧急供电,用来解决照明用电或只有一路市电缺少*二路电源,或代替发电机组构成*二电源,或做为需要*三电源的场合使用。
UPS和EPS的功能区别
EPS和UPS都具备市电旁路和逆变电路,但是EPS只具有持续供电功能,对逆变切换时间要求不高,目前大部分EPS还具备蓄电池单体检测功能。EPS在市电中断后才进行逆变输出,电脑利用率高。
而UPS一般强调其三大功能:对市电进行稳频和稳压处理;对切换时间要求较高的设备供电;净化市电。日常着重整流和逆变的双变换电路供电,电能利用率不高。但是UPS不仅仅是在断电时逆变供电,还可以在市电出现电压偏差大、浪涌等异常情况时提供稳定的电力输出,这是EPS所不具备的。
3)UPS和EPS在应用范围的不同
EPS主要用于消防类负荷以及一些对切换时间要求不高,但需要持续供电的设备。
UPS主要用于计算机、数字信息系统等对供电质量要求较高的负载。
产品原理
SKEPS系列单相EPS应急电源,是为建筑物内紧急疏散照明或重要用电设备提供集中供电的应电电源设备。
当市电正常时,由市电经过互投装置给负载供电,同时充电器给备用电池进行智能充电。当市电断电,或**过正常电压的20%时,由控制器提供逆变信号,启动逆变电源,同时互投装置将立即投切至逆变电源输出,继续提供正弦波交流电,当市电电压正常后,应急电源将自动恢复电网供电。
产品特点
1、采用集中模式、*特殊灯具;
2、双路电源自动切换,可靠性高;
3、寿合长,主机寿命20年以上;
4、采用CPU控制,保证各动作点准确;
5、LED显示和声音告警,工作状态一目了然;
6、具有过压、欠压、过温、过流、短路等保护功能;
7、智能电池充电管理功能,可实现均浮充自动转换,有效延长电池寿命;
8、自动监控电池工作状态,具有电池充放自动保护;
9、模块化结构设计,维护方便。
应急电源(EPS)系统主要由整流器、静态开关模块/手动旁路开关、控制单元及逆变器、机架、蓄电池组组成,其中逆变器是核心。整流器的作用是将交流电变换成直流电,实现对蓄电池充电及向逆变模块供电;逆变器的作用则是将直流电变换成交流电,供给负载设备稳定持续的电力;静态开关器可以设定系统工作在后备或在线两种方式,并可调整逆变器的输出与市电同步,保证负载在市电及逆变器输出间的顺利切换。手动旁路开关可将负载切换至市电并与系统隔离,这样在对系统进行维护时也不会妨碍负载设备的正常工作。监控器对整个系,并可发出告警信号,同时可通过串行口与计算机或Modem相连接,实现对供电系统的微机监控和远程监控。
广泛适用于市电中断时各类一级和特别重要负荷的交流应急供电,如各类重要计算机系统的供电;各类建筑的工作供电和消防供电;医院安全供电;交通系统高速公路、隧道、地铁、轻轨、民用机场的供电;电力系统的供电;各类不能断电的生产、实验设备的供电。是设备要求纯净正弦波高质量供电电源。